CVE-2022-33174
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit...
- Published
- Jun 13, 2022
- Updated
- Aug 3, 2024
- Assigning CNA
- mitre
- Evidence observed
- Aug 5, 2026
Primary CVSS
nvd · CVSS 3.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HModerate · next 30 days
- Percentile
- 96.5%
- Model date
- Sep 21, 2026
EPSS is a statistical estimate, not a certainty or a measure of impact. Combine it with CVSS, KEV status, exposure and your environment.
Summary
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Sources
1- CVE-2022-33174Exploit
Powertek PDU身份绕过
Responsible use
Use vulnerability information only on systems you own or are authorized to test. Kitploit links to public research metadata and does not store exploit code or malicious payloads.