CVE-2021-22681
Rockwell Multiple Products Insufficient Protected Credentials Vulnerability
- Published
- Mar 3, 2021
- Updated
- Mar 6, 2026
- Assigning CNA
- icscert
- Evidence observed
- Mar 5, 2026
Primary CVSS
nvd · CVSS 3.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HHigh · next 30 days
- Percentile
- 99.2%
- Model date
- Sep 21, 2026
EPSS is a statistical estimate, not a certainty or a measure of impact. Combine it with CVSS, KEV status, exposure and your environment.
CISA Known Exploited
This CVE appears in the CISA Known Exploited Vulnerabilities catalog.
Summary
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
Sources
1Proof-of-concept reproducing CVE-2021-22681's hardcoded-key flaw and validating a per-device mutual TLS/CRL fix over simulated EtherNet/IP, with IEC 62443-4-2 mapping.
Responsible use
Use vulnerability information only on systems you own or are authorized to test. Kitploit links to public research metadata and does not store exploit code or malicious payloads.